6ES7318-3EL01-0AB0
Product
SIMATIC S7-300 CPU 319-3 PN/DP, 中央处理器 带有 2 MB 工作存储区, 1. 接口 MPI/DP 12MBIT/S, 2. 接口 DP-MASTER/SLAVE, 3. 接口 以太网 PROFINET, 带有 2个 PORT SWITCH,必须有 MMC卡
列表价格 显示价格
客户价格 显示价格
PDF 格式的数据表 下载
服务和支持 (手册,认证,问答...) 下载
更多图片
产品
商品编号(市售编号) 6ES7318-3EL01-0AB0
产品说明 SIMATIC S7-300 CPU 319-3 PN/DP, 中央处理器 带有 2 MB 工作存储区, 1. 接口 MPI/DP 12MBIT/S, 2. 接口 DP-MASTER/SLAVE, 3. 接口 以太网 PROFINET, 带有 2个 PORT SWITCH,必须有 MMC卡
产品家族 CPU 319-3 PN/DP
西门子CPU319-3PN/DP模块
Time?of?day
Clock
Hardware?clock?(real-time?clock)
Yes
battery-backed?and?synchronizable
Yes
Deviation?per?day,?max.
10 s;?Typ.:?2?s
Backup?time
6 wk;?At?40?°C?ambient?temperature
Behavior?of?the?clock?following?POWER-ON
Clock?continues?running?after?POWER?OFF
Behavior?of?the?clock?following?expiry?of?backup?period
Clock?continues?to?run?with?the?time?at?which?the?power?failure?occurred
Operating?hours?counter
Number
4
Number/Number?range
0?to?3
Range?of?values
0?to?2^31?hours?(when?using?SFC?101)
Granularity
1?hour
retentive
Yes;?Must?be?restarted?at?each?restart
Clock?synchronization
supported
Yes
to?MPI,?master
Yes
to?MPI,?slave
Yes
to?DP,?master
Yes;?With?DP?slave?only?slave?clock
to?DP,?slave
Yes
in?AS,?master
Yes
in?AS,?slave
Yes
on?Ethernet?via?NTP
Yes;?As?client
Digital?bs
Number?of?digital?bs
0
Digital?outputs
Number?of?digital?outputs
0
Analog?bs
Number?of?analog?bs
0
Analog?outputs
Number?of?analog?outputs
0
Interfaces
Number?of?USB?interfaces
0
Number?of?parallel?interfaces
0
Number?of?20?mA?interfaces?(TTY)
0
Number?of?RS?232?interfaces
0
Number?of?RS?422?interfaces
0
Number?of?other?interfaces
1;?Ethernet,?2-port?switch,?2*RJ45
1st?interface
Interface?type
Integrated?RS?485?interface
Physics
RS?485
Isolated
Yes
Power?supply?to?interface?(15?to?30?V?DC),?max.
150 mA
Functionality
MPI
Yes
DP?master
Yes
DP?slave
Yes;?A?DP?slave?at?both?interfaces?simultaneously?is?not?possible
Point-to-point?connection
No
MPI
Transmission?rate,?max.
12 Mbit/s
Services
PG/OP?communication
Yes
Routing
Yes
Global?data?communication
Yes
S7?basic?communication
Yes
S7?communication
Yes
S7?communication,?as?client
No;?but?via?CP?and?loadable?FB
S7?communication,?as?server
Yes
DP?master
Transmission?rate,?max.
12 Mbit/s
Number?of?DP?slaves,?max.
124
Services
PG/OP?communication
Yes
Routing
Yes
Global?data?communication
No
S7?basic?communication
Yes;?I?blocks?only
S7?communication
Yes
S7?communication,?as?client
No
S7?communication,?as?server
Yes
Equidistance?mode?support
Yes
Isochronous?mode
No
SYNC/FREEZE
Yes
Activation/deactivation?of?DP?slaves
Yes
Number?of?DP?slaves?that?can?be?simultaneously?activated/deactivated,?max.
8
Direct?data?exchange?(slave-to-slave?communication)
Yes;?As?subscriber
DPV1
Yes
Address?area
Inputs,?max.
8 kbyte
Outputs,?max.
8 kbyte
User?data?per?DP?slave
Inputs,?max.
244 byte
Outputs,?max.
244 byte
DP?slave
Transmission?rate,?max.
12 Mbit/s
Automatic?baud?rate?search
Yes;?only?with?passive?interface
Address?area,?max.
32
User?data?per?address?area,?max.
32 byte
Services
PG/OP?communication
Yes
Routing
Yes;?with?interface?active
Global?data?communication
No
S7?basic?communication
No
S7?communication
Yes
S7?communication,?as?client
No
S7?communication,?as?server
Yes;?Connection?configured?on?one?side?only
Direct?data?exchange?(slave-to-slave?communication)
Yes
DPV1
No
Transfer?memory
Inputs
244 byte
Outputs
244 byte
2nd?interface
Interface?type
Integrated?RS?485?interface
Physics
RS?485
Isolated
Yes
Power?supply?to?interface?(15?to?30?V?DC),?max.
200 mA
Functionality
MPI
No
DP?master
Yes
DP?slave
Yes;?A?DP?slave?at?both?interfaces?simultaneously?is?not?possible
PROFINET?IO?Controller
No
PROFINET?IO?Device
No
PROFINET?CBA
No
Open?IE?communication
No
Web?server
No
DP?master
Transmission?rate,?max.
12 Mbit/s
Number?of?DP?slaves,?max.
124
Services
PG/OP?communication
Yes
Routing
Yes
Global?data?communication
No
S7?basic?communication
Yes;?I?blocks?only
S7?communication
Yes
S7?communication,?as?client
No
S7?communication,?as?server
Yes;?Connection?configured?on?one?side?only
Equidistance?mode?support
Yes
Isochronous?mode
Yes;?OB?61?-?isochronous?mode?is?possible?either?on?DP?or?PROFINET?IO?(not?simultaneously)
SYNC/FREEZE
Yes
Activation/deactivation?of?DP?slaves
Yes
Number?of?DP?slaves?that?can?be?simultaneously?activated/deactivated,?max.
8
Direct?data?exchange?(slave-to-slave?communication)
Yes;?As?subscriber
DPV1
Yes
Address?area
Inputs,?max.
8 kbyte
Outputs,?max.
8 kbyte
User?data?per?DP?slave
Inputs,?max.
244 byte
Outputs,?max.
244 byte
DP?slave
GSD?file
The?latest?GSD?file?is?available?at:/profibus-gsd
Transmission?rate,?max.
12 Mbit/s
Automatic?baud?rate?search
Yes;?only?with?passive?interface
Address?area,?max.
32
User?data?per?address?area,?max.
32 byte
Services
PG/OP?communication
Yes
Routing
Yes;?with?interface?active
Global?data?communication
No
S7?basic?communication
No
S7?communication
Yes
S7?communication,?as?client
No
S7?communication,?as?server
Yes;?Connection?configured?on?one?side?only
Direct?data?exchange?(slave-to-slave?communication)
Yes
DPV1
No
Transfer?memory